2.4.3
Multi-speed operation [Pr. 4 to 6, 24 to 27, 232 to 239]
Can be used to change the preset speed in the parameter
with the contact terminals.
Each speed can be selected by merely turning ON or OFF
the contact signals (RH, RM, RL, REX signals).
Refer to page 48 for the detail of input signal combinations.
[Pr.]
4
Multi-speed setting (high speed)
5
Multi-speed setting (middle speed)
6
Multi-speed setting (low speed)
24
Multi-speed setting (speed 4)
25
Multi-speed setting (speed 5)
26
Multi-speed setting (speed 6)
27
Multi-speed setting (speed 7)
232
Multi-speed setting (speed 8)
233
Multi-speed setting (speed 9)
234
Multi-speed setting (speed 10)
235
Multi-speed setting (speed 11)
236
Multi-speed setting (speed 12)
237
Multi-speed setting (speed 13)
238
Multi-speed setting (speed 14)
239
Multi-speed setting (speed 15)
(1) 3-speed setting [Pr. 4 to 6]
The inverter operates at frequencies set in [Pr. 4]
when RH signal is ON, [Pr. 5] when RM signal is ON
and [Pr. 6] when RL signal is ON.
In the initial setting, if two or three signals are
simultaneously selected, priority is given to the set
frequency of the lower signal.
For example, when the RH and RM signals turn ON,
the RM signal [Pr. 5] has a higher priority.
Initial
Name
Value
60Hz
30Hz
10Hz
9999
9999
9999
9999
9999
9999
9999
9999
9999
9999
9999
9999
The priority of the frequency command by the external
signals is "Jog operation
Terminal 4 analog input
analog input".
Valid in the External operation mode [Pr. 79 = 0, 2] or PU/
external combined operation mode [Pr. 79 = 3, 4].
Multi-speed parameters can also be set in the PU or
External operation mode
.
Setting Range
0 to 400Hz
Frequency when RH turns ON
0 to 400Hz
Frequency when RM turns ON
0 to 400Hz
Frequency when RL turns ON
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
Frequency from 4 speed to 15 speed can be set
0 to 400Hz, 9999
according to the combination of the RH, RM, RL and
0 to 400Hz, 9999
REX signals.
0 to 400Hz, 9999
0 to 400Hz, 9999
9999: Not selected
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
(2) Multi-speed setting for 4 or more speeds
[Pr. 24 to 27, 232 to 239]
Frequency from 4 speed to 15 speed can be set
according to the combination of the RH, RM, RL and
REX signals. Set the running frequencies in [Pr. 24 to
27, 232 to 239] (In the initial value setting, speed 4 to
speed 15 are unavailable).
For the terminal used for REX signal input, set 8 in
any of [Pr. 178 to 189 input terminal function selection]
to assign the function.
216
PARAMETER
common
(common)
Multi-speed operation
Pulse train input
Description
Terminal 2