2.4.5
Remote setting function [Pr. 59]
When "1 to 3" is set in [Pr. 59], the functions of the RH, RM
signals are changed to input function of remote setting.
Setting is available for both PU operation mode and External
operation mode.
Note that this is different with a function of motorized speed
setter (FR-FK).
Initial
Setting
[Pr. ]
Name
Value
Range
Remote
59
function
0
selection
1)During acceleration
Set frequency increases when RH signal turns ON.
Speed of increase depends on [Pr. 44 Second
acceleration/deceleration time].*1
When RH signal turns OFF, increase of set frequency
is stopped and the set frequency at that moment is
retained.
2)During deceleration
Set frequency decreases when RH signal turns ON.
Speed of decrease depends on [Pr. 45 Second
deceleration time]. When "9999" is set to [Pr. 45], the
speed of decrease is equal to the [Pr. 44] setting.*1
When RH signal turns OFF, decrease of set
frequency is stopped and the set frequency at that
moment is retained.
Inverter
Forward
rotation
STF
Acceleration
RH
Deceleration
RM
10
Clear
RL
2
SD
5
Connection
diagram for remote setting
Description
RH, RM, RL
Frequency
signal
setting storage
function
function
Multi-Speed
0
Setting
Remote
1
Yes
setting
Remote
2
No
setting
No
Remote
(Turning STF/STR
3
setting
OFF clears remotely-
set frequency)
*
0Hz
ON
Acceleration
(RH)
Deceleration
(RM)
Clear (RL)
Forward
rotation (STF)
Power supply
External operation frequency (other than multi-speed) or PU running frequency
common
(common)
3)Output frequency
External operation
Frequency set with RH and RM operation +
external operation frequency other than multi-
speed (When making input compensation
(terminal 1), set [Pr. 28 = 1].)
PU operation
Frequency set with RH and RM operation +
PU operation frequency
4)Frequency setting storage
When [Pr. 59 = 1], the remotely-set frequency is
stored every minute after turning OFF (ON) of both
the RH (acceleration) and RM (deceleration) signals.
The set frequency when STF (STR) turned OFF is
also stored. (The frequency is overwritten if the latest
frequency is different from the past frequency when
comparing the two. The state of the RL signal does
not affect storing.)
When [Pr. 59 = 2, 3], set frequency is not stored.
Therefore turning OFF the power and then turning
ON will make the set frequency to 0Hz.
5)Setting Clear
Remotely-set frequency is cleared to 0Hz when RL
signal turns ON with [Pr.59 = 1 or 2], or when
STF(STR) signal turns OFF with [Pr. 59 = 3].
*1
When the acceleration or deceleration signal switches
on, the set frequency varies according to the slope set in
[Pr. 44] or [Pr. 45]. The acceleration/deceleration time of
output frequency is as set in [Pr. 7, 8]. Therefore, the
longer preset time is used to vary the actual output
frequency.
*2
Multi-speed operation does not function when remote
setting function is selected ("1 to 3" is set in [Pr. 59]).
*3
Remote setting function does not function when Jog
operation or PID control is selected.
*4
Keeping RH signal ON does not increase frequency
beyond the maximum frequency.
*5
The wiring length should be within 30m.
ON
ON
ON
ON
ON
ON
226
PARAMETER
When [Pr. 59 = 1]
When [Pr. 59 = 1, 2]
When [Pr. 59 = 3]
When [Pr. 59 = 2, 3]
ON
ON
Time
ON
ON