(2) Pulse train form selection (PP, NP signal) [Pr. 428]
Command pulse can be changed according to the
positioning unit as in the table below.
Command Pulse Train Form
Forward rotation pulse train
Reverse rotation pulse train
Pulse train + rotation direction sign
A phase pulse train
B phase pulse train
Forward rotation pulse train
Reverse rotation pulse train
Pulse train + rotation direction sign
A phase pulse train
B phase pulse train
(3) Interface of the positioning unit and inverter
When running the inverter by each positioning unit,
interface of the positioning command pulse train
need to be matched.
Output Type
Open collector
Differential line driver
At Forward
Rotation
PP
NP
PP
L
NP
PP
NP
PP
NP
PP
NP
H
PP
NP
Hardware Configuration
Connect
Command unit
externally
VDD
OPC
PP(NP)
SD
*: Wiring length : max. 2m
Command unit
Do not
connect
VDD
OPC
PP(NP)
PGP
(PGN)
*: Wiring length : max. 10m
At Reverse
Setting
Rotation
[Pr. 428]
0
(factory
setting)
1
H
2
3
4
L
5
Inverter (FR-A7AL)
+24
Max. 200kpps
Inverter (FR-A7AL)
+24
Max. 500kpps
314
PARAMETER
Remarks
QD75D(CW/CWW mode)
(Note) If (CW/CWW mode) and (PLS/
SIGN mode) are mistaken, the motor
runs only in one direction.
QD75D (PLS/SIGN mode)
Counted after multiplying by four.
Set the pulse train frequency multiplied
by four to 500kpps or less with the
differential driver type and to 200kpps or
less with the open collector type.
Counted after being multiplied by four.
Set the pulse train frequency multiplied
by four to 500kpps or less with the
differential driver type and to 200kpps or
less with the open collector type.
Input Pulse Frequency