Parameter
Server encryption
Encryption algorithm
CBC
NMS IP address
NMS port number
Pre-shared password
----End
5.4.4.3 Setting Communications Parameters (SNMP Protocol)
Context
●
●
●
●
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
Issue 01 (2022-12-30)
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you connect
a unit to a network management system (NMS).
One unit supports concurrent access of up to 6 NMSs through SNMP.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
This parameter is configurable when Link mode
involves Server.
NOTE
In the third-party NMS scenario, if the third-party NMS does
not have a certificate or does not support encryption, you are
advised to set this parameter to Disable for non-encrypted
connection. For security purposes, encryption is enabled by
default. You can configure encryption based on actual
requirements and security scenario evaluation.
Specifies whether to use the CBC encryption algorithm.
After the parameter setting is changed, the system
automatically restarts. Exercise caution with the setting.
Enter the actual IP address of the NMS. The IP
addresses of the display board, client NMS, and server
NMS must be unique.
This parameter is configurable when Link mode
involves Client.
This parameter is configurable when Link mode
involves Client.
● Connecting to the NetEco: Set this parameter to
32907 if Client encryption is enabled, or set it to
32906 if Client encryption is disabled.
● Connecting to other NMSs: You are advised not to
change the value. In special cases, set this
parameter based on the site requirements.
Secondary authentication password used for Modbus-
TCP connection.
5 Power-On Commissioning