Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, and set
Air-side differential pressure sensor type to 0~500 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Parameter
Indoor fan control
type
Indoor fan pressure
difference setpoint
Air-side differential
pressure sensor type
----End

5.4.3 (Optional) Setting Teamwork Parameters

Prerequisites
The teamwork group number and addresses for the smart cooling products have
been set as follows:
Issue 01 (2022-12-30)
Teamwork group num: Group the smart cooling products in adjacent areas as
one, that is, assign one teamwork group number for them. At most four
teamwork control groups can be set (1–4).
System address: The address (configurable range: 1–32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
● R/S air temp diff rate ctrl: controls the indoor fan
speed based on the rate of temperature difference
between return air and supply air.
● R/S air temp diff ctrl: controls the indoor fan speed
based on the temperature difference between return
air and supply air.
● Cooling source opening ctrl: controls the indoor fan
speed based on the opening of the chilled water
valve.
● Pressure diff ctrl: controls the indoor fan speed
based on the pressure difference.
● Return air temp ctrl: controls the indoor fan speed
based on the return air temperature.
● Supply air temp ctrl: controls the indoor fan speed
based on the supply air temperature.
Specifies the control value of indoor fan pressure
difference.
NOTE
This parameter is displayed when Indoor fan control type is
set to Pressure diff ctrl.
Select the proper differential pressure sensor type
based on the measurement range of the differential
pressure sensor.