Startup And Configuration; Fe Monitoring Network Cable (Modbus-Tcp Protocol/Snmp Protocol); Optional) Setting Communications Parameters; Startup And Commissioning - Huawei NetCol8000-A Series Quick Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A Series:
Table of Contents

Advertisement

(Optional) Setting communications parameters

10.4
RS485 Monitoring Network Cable (Modbus-RTU Protocol)
a. On the home screen, choose Settings > Comm Settings > Modbus Settings. The value
should be consistent with that set on the EMS.
b. Set the communication address. The communication addresses of two smart cooling
products connecting to the same EMS must be unique.
c. Set the RS485 monitoring grouping.
If there is no teamwork control, set the "RS485 monitoring grouping" of each smart
cooling product to "Enable".
For CAN networking and no grouping scenario, set the "RS485 monitoring grouping" of
the last smart cooling product to "Enable".
• For CAN networking and grouping scenario, set the "RS485 monitoring grouping" of the
last smart cooling product in each teamwork control group to "Enable".

FE Monitoring Network Cable (Modbus-TCP Protocol/SNMP Protocol)

a. On the home screen, choose Settings > Comm Settings > IP Settings. the IP assigning
mode is set to Manual. Set IP address, Subnet mask, Gateway according to the actual plan.
b. On the home screen, choose Settings > Comm Settings > Modbus Settings. Set Link
mode to Server and client or Client, and set Client encryption to Enable.
c. Enter the actual IP address of the EMS.
d. When Client encryption is set to Enable, set NMS port number to 32907.
If the DHCP server is configured on the NMS, select DHCP auto. If no, set this
parameter to Manual.
The encryption mode must be the same as it on the NMS.
11

Startup and Commissioning

Download the Service Expert app from Huawei app store and runs on Android. Apply for
permission after downloading the app.
Ensure that no combustion-supporting materials (air or additives) enter the air conditioning
system during commissioning. Huawei shall not be liable for any risks and losses thus incurred.
33