4.5.2 Connecting an Equipotential Ground Cable

Context
Procedure
Step 1 A ground cable must be routed from the equipotential bonding point of the
cabinet to the ground. The following figure shows the equipotential bonding point
of the cabinet.
Figure 4-20 Equipotential ground point (using top cabling as an example)
----End

4.5.3 Connecting Power Cables

Context
Procedure
Step 1 Connect the PE cable to the ground screw on the cabinet.
Step 2 Connect wiring terminals of the L1, L2, and L3 wires of the input power cable
respectively to the corresponding terminals of the external power cable.
Issue 01 (2022-12-30)
Cable colors in this document are for reference only. The actual cable colors
may vary.
The equipment must be grounded as required by local electrical specifications.
In the example, the equipotential ground cable is routed from the top of the
cabinet. In the bottom cabling mode, the ground cable is routed through the
cabinet bottom.
Cables must be routed in through cable clips.
Route and bind the cables along the beams or columns of the unit.
The neutral wire is not required for the power input to the product. If a five-
core cable is used, cut the blue neutral wire onsite and wrap the exposed part
using insulation tape.