Huawei FusionCol8000-C210 User Manual page 87

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Menu
System
Settings
Issue 01 (2022-12-30)
Parameter
Cold aisle
temperature and
humidity sharing
Hot aisle
temperature and
humidity sharing
Motorized
damper
Dual power
supply setting
Password
required for start
or shutdown
onsite
System power
limit
Altitude
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Power-On Commissioning
Description
This function can be enabled only when at
least one smart cooling product in the
teamwork group is equipped with cold aisle
T/H sensors. If this function is enabled, the
master unit in the teamwork group collects
the cold aisle temperature and humidity
values from all units equipped with cold
aisle sensors, and synchronizes the
temperature and humidity control type and
setpoints to all slave units.
This function can be enabled only when at
least one smart cooling product in the
group is equipped with hot aisle T/H
sensors. If this function is enabled, the
master unit in the teamwork group collects
the hot aisle temperature and humidity
values from all units equipped with hot aisle
sensors, and synchronizes the temperature
and humidity control type and setpoints to
all slave units.
● Disable: The air damper function of the
unit is disabled.
● AO Ctrl: Select AO Ctrl for AO-type air
dampers.
Set this parameter as required.
● Primary power only: Select this option
when the dual-power model is connected
to the primary power only.
● Primary power first: Select this option
when the dual-power model is connected
to two power supplies.
● No: No password is required for startup
or shutdown.
● Yes: A password is required for startup
and shutdown.
This parameter ensures that the total
operating power of the system is always
below the preset value.
NOTE
Set the maximum rated power of the system
based on the actual cooling requirements of the
equipment room.
Set this parameter based on the actual
altitude.
79