10.8 Replacing a Liquid Level Detector

Prerequisites
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Exercise caution because the device is still energized after it is shut down on the
home screen of the display module.
Step 2 Open the electric control box, and switch off the active circuit breaker (QF1) and
standby circuit breaker (QF2).
Step 3 Remove the air filter.
Step 4 Remove the two butterfly nuts from the liquid level detector fastener, and take
out the liquid level detector and its fastener.
Figure 10-10 Taking out a liquid level detector
Step 5 Remove the liquid level detector.
1.
2.
Issue 01 (2022-12-30)
Configuration File Encryption Password, tap Upload to import the data to
the WebUI.
A liquid level detector needs to be replaced.
A spare liquid level detector of the same model is available and functional.
Tool: Phillips screwdriver
NO TICE
Remove the interconnection terminal, loosen the nut on the low liquid level
detector, and take out the detector from the other side.
Remove the protective cover from the high liquid level detector.