Huawei FusionCol8000-C210 User Manual page 29

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Table 2-2 Indicator and buzzer status description
Indicator
Green
Yellow
Red
Note: Hold down the SW button on the main control module for about 1s. In all
the preceding states, the indicator blinks at 1 Hz (on for 0.5s and off for 0.5s).
Functions
Function
Single unit
control
Operations
Four remote
functions
Issue 01 (2022-12-30)
Buzzer
No buzzing
Intermittent
buzzing
Constant
buzzing
Description
Each unit has an independent control system to ensure normal
and high-precision operation.
Users can set parameters and query status on the 7-inch true-
color touchscreen.
The module supports the four remote functions when it
connects to the NMS.
● Telemetry: measures the supply air temperature, return air
temperature, supply air humidity, return air humidity, and
working status of the unit.
● Teleadjust: adjusts the temperature, humidity, and alarm
threshold.
● Teleindication: generates alarms for the startup/shutdown,
overvoltage/undervoltage, high/low return air temperature,
high/low return air humidity, air filter normal/blocked, and
fan normal/faulty state.
● Telecontrol: controls startup/shutdown.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Running Status
The unit is operating properly, or there is a
warning.
There is an unacknowledged major alarm.
There is an unacknowledged critical alarm.
2 Product Composition
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-c210h4

Table of Contents