FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Figure 4-11 Combining units
Step 2 Secure the connecting kits in the connection positions on the fan side in a similar
way. (Secure the top connecting plates to the holes in the middle position shown
in the figure using M6 bolt assemblies.)
----End

4.3.5 Securing a Unit

1.
Issue 01 (2022-12-30)
NO TE
● Obtain the connecting plates and screws according to the packing list.
● Ensure that the vertical distance between the top of each unit and the floor is 2450 mm
(±2 mm) and that the tops of all units are on the same horizontal plane.
● A distance of at least 15 mm must be reserved between combined units.
Secure the unit to the floor using four M12 expansion bolts, and install
anchor baffle plates. The following figure shows the mounting hole
dimensions on the floor.
Figure 4-12 Hole dimensions on the floor (unit: mm)
NO TE
If you need to secure the unit to a base, see the base dimensions drawing. Secure it to
the base using four M12x45 bolt assemblies and install anchor baffle plates.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
45