RMS-SNMP01B SNMP Card
User Manual
Issue
10
Date
2020-03-20
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei RMS-SNMP01B

  • Page 1 RMS-SNMP01B SNMP Card User Manual Issue Date 2020-03-20 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    About This Document About This Document Purpose This document describes the RMS-SNMP01B in terms of its features, appearance, installation, usage, and operation. The RMS-SNMP01B is an optional communications card which is designed for the UPS2000-G-(1 kVA-3 kVA) and UPS2000-A-(1 kVA-3 kVA) series.
  • Page 4 The output terminal of 3 kVA UPS changed to output socket (C19). Issue 04 (2016-01-20) Updated the 10 Changing the SSH Access Password. Issue 03 (2015-07-27) Updated the 4.2.2 Setting Internet Explorer Options. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 5 RMS-SNMP01B SNMP Card User Manual About This Document Issue 02 (2015-05-10) The software is upgraded. Issue 01 (2014-10-27) This is the first release. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 6: Table Of Contents

    4.5.1 Logs ..................................21 4.5.2 Performance Data ..............................22 4.5.3 Historical Alarms ..............................23 4.6 Configuration Page ..............................24 4.6.1 Comm. Config Page ..............................24 4.6.2 User Mgmt. Page ..............................28 Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 7 5.2 Applying for Access Rights ............................45 5.3 Managing the UPS ..............................45 6 Managing the UPS by Using the NMS Complying with Huawei Standard ....46 6.1 SNMP Card Versions ..............................46 6.2 Installing the UPS MIB Library ..........................46 6.3 Managing the UPS by Using the NMS ........................
  • Page 8: Safety Information

    UPS output voltage level or frequency. Doing so may affect the power supply to equipment. Exercise caution when setting battery parameters. Incorrect settings will affect the power supply and battery lifespan. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Overview

    The SNMP card allows users to remotely manage the UPS by using an NMS, Huawei NetEco, or a web browser on a computer network. A maximum of 16 SNMPv3 users and 80 NMS users can manage the UPS. A maximum of 2 WebUI users can manage the UPS online.
  • Page 10: Port Description

    Steady on: A network cable is connected. Yellow Blinking: The card is communicating with the indicator network. Port for This port connects to temperature and humidity sensor southbound or external dry contact card. device Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 11 Table 2-2 lists the port definition. Table 2-2 Port to a temperature and humidity sensor Port Pin No. Signal Port Type CNRJ2 RS485+ (A) RJ45 RS485– (B) 12V_OUT RS485+ (A) RS485– (B) Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 12: Installation And Basic Settings

    SNMP card, preventing ESD from damaging the SNMP card. Hold the edges of the SNMP card when you move or install it.  Wear ESD gloves when you install the SNMP card. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 13: Installing The Snmp Card

     Set the temperature and humidity sensor address to 1 (DIP switch 1 is ON, the other DIP switch is OFF, as shown in Figure 3-2) and baud rate to 9600. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 14: External Dry Contact Card

    (7) Reset button switch base The external dry contact card connects to the UPS over an SNMP card. Figure 3-4 shows how to connect cables to the external dry contact card. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 15 3-5shows the DIP switch status of the RMS-RELAY02B. 1 is set to ON and other toggle switches are set to OFF. The baud rate is set to 9600. Figure 3-5 DIP switch Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 16: Managing The Ups On The Webui

    4.1 Introduction to Web Pages The user interface (UI) snapshots in this document correspond to the software version UPS2000 V200R001C01SPC300. The UI snapshots are subject to change without notice. Contact Huawei technical support to obtain the latest snapshots if you need.  Monitoring page −...
  • Page 17: Preparations For Login

    Figure 4-1 Security warning After you select Continue to this website (not recommended) in Figure 4-1, click Certificate Error in the upper right corner. A dialog box is displayed, as shown in Figure 4-2. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 18 4-3.  The security certificate presented by this website was not issued by a certificate authority.  The security certificate presented by this website has expired or is not yet valid. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 19 − Method 1: In Internet Explorer, choose Internet Options > Advanced. Deselect Warn about certificate address mismatch*, as shown in Figure 4-5. − Method 2: Apply for a digital certificate again. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Setting Internet Explorer Options

    User Manual 4 Managing the UPS on the WebUI Figure 4-5 Setting Internet options 4.2.2 Setting Internet Explorer Options Choose Internet Options > Advanced and set options, as shown in Figure 4-6. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 21 Choose Page > Compatibility View Settings and add the SNMP card IP address. If the SNMP card IP address is not changed, add 192.168.0.10, as shown in Figure 4-7. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 22: Privacy Statement

    Figure 4-7 Adding compatibility view settings 4.2.3 Privacy Statement  Before performing any maintenance or change operations, Huawei engineers must obtain the formal written authorization from the customer, and must perform operations in compliance with local laws and regulations. ...
  • Page 23: Webui Login

    On the WebUI, only part of the email address is displayed. For example, support@huawei.com is displayed as su****t@huawei.com. The email password is displayed as ciphertext *****. The system provides the personal data encryption protection. The email address and password are encrypted using a secure encryption algorithm with a cipher key.
  • Page 24: Monitoring Page

    After login, the Monitoring page is displayed, showing the UPS model and ESN. The UPS information area presents Active Alarms, as shown in Figure 4-9. Click the device name on the upper left corner to edit it, or edit it by pressing Enter. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 25 UPS information area Provides four pages: Active Alarms, Real-Time Data, Param. Settings, and Control. Communication status bar Displays the current user name, Ethernet connection status, IP address of the SNMP card, and time. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Real-Time Data Page

    Enter a value within the range. Table 4-3 lists the default values and value ranges. The Param. Settings is active only the SNMP card is equipped with a temperature and humidity sensor. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Control Page

    0–40% RH 4.4.4 Control Page In the UPS information area, choose Control > System Commands and Tests, and you can start or shut down the UPS, as shown in Figure 4-12. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Query Page

    4 Managing the UPS on the WebUI Figure 4-12 Control page 4.5 Query Page 4.5.1 Logs The Logs page provides user operation information, as shown in Figure 4-13. It lists a maximum of 1000 records. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 29: Performance Data

    UPS. The time interval is configured in Config > Performance Data. The fault value is 30s, as shown in Figure 4-15. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 30: Historical Alarms

    Query. The page displays historical alarms in the specified time period for the selected UPS, as shown in Figure 4-17. Figure 4-17 Historical Alarms Query page Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 31: Configuration Page

    This function is disabled by default. If this function is enabled, you can access the SNMP card in the internal network through the external network by using a router with the NAT function. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 32 Figure 4-19 Delete the sender's email configurations Configuring Alarm Notification Settings On the Alarm Notification Settings page, you can choose whether to enable email notifications, timely reminder, and select alarm severities (critical, major, minor, or all), as Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 33 Shutdown, and there is a 12–24 V DC input. If the UPS is faulty, it does not perform the startup command when DI is set to Startup. Rectify the UPS fault first. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 34 DI Status Event or Not There is a Startup 12–24 V DC input. Startup There is a 12–24 V DC input. Startup There is no input. Startup There is no input. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 35: User Mgmt. Page

    Click Modify. The Modify User dialog box appears, as shown in Figure 4-23. You can change the password, email language, email address. The initial password is required when you make changes. Click Submit to submit the changes. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 36: Site Config Page

    The SNMP card supports Secure Sockets Layer (SSL) certificate import, as shown in Figure 4-28. The certificate is used for SSL encryption protection during WebUI login. Apply to a third-party institution for the certificate. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 37 RMS-SNMP01B SNMP Card User Manual 4 Managing the UPS on the WebUI Figure 4-25 Site Config page Figure 4-26 Time synchronization from the NTP server Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 38: Performance Data Page

    4.6.5 SNMP On the SNMP tab, you can configure the SNMP version, SNMP port, SNMPv1&SNMPv2c read and write communities, SNMPv3 user and NMS address and permission setting, as shown in Figure 4-30. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 39 SNMPv1&SNMPv2c is used, the correct read/write community name must be configured for the NMS to connect to the SNMP card.  The standard encryption algorithms MD5 and DES have security risks. You are advised to use the secure encryption algorithms SHA and AES. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 40 SNMP card. The read community must be different from the write community. Figure 4-32 Page for setting read and write communities for SNMPv1&SNMPv2c Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 41 NMS complying with the RFC1628 standard, such as UNMS of Generex, to manage the UPS remotely. Click Download HUAWEI-UPS-MIB to download the MIB file which allows a third-party NMS complying with Huawei standard to manage the UPS remotely. ...
  • Page 42: Rccmd

    4 Managing the UPS on the WebUI Figure 4-34 Add NMS Address Info dialog box Figure 4-35 Add SNMP TRAP If you use Huawei NetEco, set Trap port to 162. 4.6.6 RCCMD The UPS2000 SNMP card integrates the functions of the Generex RCCMD server: ...
  • Page 43 Enabled upon first login. After you submit successfully, the page refreshes. The controls such as SSL Encrypted Transmission and Client Configuration will be displayed on the page, as shown in Figure 4-38. Figure 4-37 RCCMD shutdown disabled Figure 4-38 RCCMD shutdown enabled Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 44 Figure 4-40 SSL encrypted transmission disabled Event Configuration The SNMP card supports 17 alarm events, and a maximum of 50 jobs can be added for each event, as shown in Figure 4-41. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 45 Button for deleting all You can delete all jobs of the event by jobs clicking this button. Figure 4-42 shows the buttons after one event is expanded and Table 4-7 describes these buttons. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 46 RCCMD Shutdown: You need to specify the RCCMD client IP address and port. When the RCCMD client receives the job, it will shut down the terminal which is installed with the RCCMD software. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 47 RCCMD Execute: Specify the RCCMD client IP address, port, and command to be executed. For example, enter SHUTDOWN, and the RCCMD client will shut down the terminal which is installed with the RCCMD software after receiving the message. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 48 Table 4-8 lists the signal names that can be entered. Figure 4-46 RCCMD TRAP Table 4-8 RCCMD TRAP signal Signal Name Description Unit in the UPS #MODEL Device name (UPS ESN) Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 49 At X seconds remaining time: When the battery backup time has only X seconds left, the job will be sent to the RCCMD client once. X and Y are variables and stand for time. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 50: Maintenance Page

    On the main menu bar, click Maintenance. The Maintenance page is displayed, which provides the following four options, as shown in Figure 4-48.  Operation Record Maintenance  Performance Data Maintenance  Historical Alarm Maintenance  Serviceable Data Maintenance Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 51: Upgrade Page

    On the main menu bar, click Maintenance. The Upgrade page is displayed, as shown in Figure 4-49. Figure 4-49 Upgrade page For details about the upgrade, see chapter 11 Upgrading the SNMP Card. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Managing The Ups By Using The Imanager Neteco 1000U

    You can apply for access rights over a web browser. For details, see 4.6.5 SNMP. 5.3 Managing the UPS For details about how to manage the UPS by using the iManager NetEco 1000U, see the product documentation related to iManager NetEco 1000U V100R002C00. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 53: Managing The Ups By Using The Nms Complying With Huawei Standard

    Download the MIB files on the web browser. For details, see section 4.6.1 Comm. Config Page. When you load the MIB library by using the NMS, load the HUAWEI-MIB-V3.34.mib file and then the HUAWEI-UPS-MIB.mib file. For details, see the NMS user manual. 6.3 Managing the UPS by Using the NMS 6.3.1 Applying for Access Rights...
  • Page 54: Managing The Ups By Using The Nms Complying With Rfc1628 Standard

    Take the UNMS of Generex as an example. The method for managing the UPS by using the UNMS is the same as the method for managing other devices by using the UNMS. For details, see the UNMS user manual. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 55: Protecting The Server By Using Netshutdown

    One UPS system can support a maximum of 16 pieces of NetShutdown software. For details about how NetShutdown manages the UPS status, see the product documentation related to NetShutdown V100R002C00. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 56: Protecting The Server By Using The Rccmd Software

    Figure 9-1.  If encryption is disabled, you do not need to select the encrypted transmission.  All configurations take effect only after restart. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 57: Ups Alive Check Function

    Send the message indicating that the inverter is on. Step 6 On the RCCMD client, you can check the log in the upper left corner of the RCCMD client page. ----End 9.3 UPS Alive Check Function Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 58 1800s and detection is performed 100 times, as shown in Figure 9-2. Figure 9-2 Heartbeat detecting mode on the RCCMD client You can also manually detect heartbeat by clicking Run alive check now..., as shown in Figure 9-3. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 59 RMS-SNMP01B SNMP Card User Manual 9 Protecting the Server by Using the RCCMD Software Figure 9-3 Detecting heartbeat manually Figure 9-4 Detecting heartbeat manually and successfully ----End Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 60: Troubleshooting

    Check the browser version and the SNMP card IP address that you have entered in the address bar. SNMP card problems If the fault persists after the preceding checks, replace the SNMP card. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 61: Upgrading The Snmp Card

    V200R001C31SPC100 and later versions, the upgrade package does not need to be decompressed. Select the compressed package whose file name extension is .tar.gz. Step 2 Click Send. The "File loading may take several minutes. Continue?" message is displayed, as shown in Figure 11-2. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 62 11-4.  When Upgrade progress reaches 100% and Upgrade Result is Inactive, the upgrade is complete, as shown in Figure 11-5. Then the software restarts. Figure 11-4 Activate upgrade package page Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 63 If a power failure occurs during the upgrade, power on the UPS and SNMP card again. After you log in to the WebUI again, click Go to Step 3 to perform the upgrade again, as shown in Figure 11-7 (you can skip Step Step 2, and Step Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 64 RMS-SNMP01B SNMP Card User Manual 11 Upgrading the SNMP Card Figure 11-7 Upgrade failure scenario 2 ----End Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 65: Changing The Ssh Access Password

    Use the password with certain complexity. Avoid using the preset password or low-complexity passwords that are prone to attacks and cracking by unauthorized users, which will affect the device security. To ensure Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 66: Changing An Authentication Password

    Step 2 Run the passwd enspire command to change the password of the enspire user. Step 3 Enter a new password and re-enter it as instructed and press Enter. Figure 12-1 shows the operation screen. Figure 12-1 Changing the password of the enspire user Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 67 Enter. Figure 12-3 shows the operation screen. Record and keep the password properly. If you forgot the password, you cannot access the SNMP card through SSH. Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 68 RMS-SNMP01B SNMP Card User Manual 12 Changing the SSH Access Password Figure 12-3 Changing the password of the root user ----End Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 69: A Acronyms And Abbreviations

    Hypertext Transfer Protocol Secure message digest algorithm 5 management information base Network Address Translation Network Management System RJ11 Registered Jack 11 Registered Jack 45 RJ45 Recommended Standard 485 RS485 secure hash algorithm Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 70 RMS-SNMP01B SNMP Card User Manual A Acronyms and Abbreviations Simple Network Management Protocol SNMP Secure Shell Secure Sockets Layer uninterruptible power system Issue 10 (2020-03-20) Copyright © Huawei Technologies Co., Ltd.