Replacing A Condensate Pump - Huawei FusionCol8000-C210 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
3.
Step 6 Install a new liquid level detector and connect its cables.
Step 7 Install the air filter.
Step 8 Power on the device and tap Start on the home screen. Ensure that the smart
cooling product is running properly without any alarms.
----End

10.9 Replacing a Condensate Pump

Prerequisites
Before replacing the condensate pump, drain water from the water pan
completely.
Context
The condensate pump needs to be maintained from the air return side.
Issue 01 (2022-12-30)
Remove the cable from the high liquid level detector, remove the screws from
the liquid level detector using a Phillips screwdriver, and take out the high
liquid level detector.
Figure 10-11 Removing a liquid level detector
A condensate pump needs to be replaced.
A spare condensate pump of the same model is available and functional.
Tools: flat-head screwdriver, Phillips screwdriver, socket wrench
CA UTION
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Parts Replacement
131

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-c210h4

Table of Contents