FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Step 8 Remove the hose clamp from the condensate pump using a flat-head screwdriver,
and remove the condensate pump.
Figure 10-13 Removing the water inlet pipe and condensate pump
Step 9 Install a new condensate pump and secure it using hose clamps.
Step 10 Connect the water pipes and secure them using hose clamps.
Step 11 Connect the power cable terminal of the condensate pump.
Step 12 Remove the blockage from the water pipe and install the air filter.
Step 13 Power on the unit, tap Start on the home screen, choose Maintenance >
Performance Maintenance, and clear the runtime of the condensate pump.
Step 14 Tap Start on the home screen and check that the smart cooling product is running
properly and no alarm is generated.
----End
10.10 Replacing a Display Module
Prerequisites
●
●
Context
Recommended tools: Phillips screwdriver (M4), ESD gloves
Issue 01 (2022-12-30)
A display module needs to be replaced.
A spare display module of the same model (or BOM number) as the faulty
display module is available.
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Parts Replacement
133