Injecting Water To Expel Gas; Leakage Test With Water - Huawei FusionCol8000-C210 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Step 4 Open the exhaust valve using a screwdriver, and close the valve when there is no
gas flowing through the valve. Then you can perform the following operations.
Do not exhaust nitrogen in the confined space. Ventilate the equipment room.
Step 5 After the leakage test has been performed and gas has exhausted, re-wrap the
needle valve with thermal insulation foam.
----End
Troubleshooting

4.4.4 Injecting Water to Expel Gas

Prerequisites
Procedure
Step 1 Open the main water inlet valve of the unit.
Step 2 Ensure that the needle valve and exhaust valve on the pipe are closed and the
chilled water valve is in the 100% state.
Step 3 Gradually open the exhaust valves. Air and chilled water flow out of the air
exhaust hose together.
Step 4 Adjust the exhausting speed until no bubble flows out of the hose.
Step 5 After gas is expelled, manually turn the chilled water valve to the 0 state.
Step 6 Close the exhaust valve.
----End

4.4.5 Leakage Test with Water

Issue 01 (2022-12-30)
NO TICE
If the pressure decreases, apply soapy water on the pipes, especially screw
threads to check for any leakage.
If the pressure is stable, wrap all water pipes and connectors with thermal
insulation foam.
Nitrogen must be expelled before injecting water.
To avoid blockage of the heat exchanger in the smart cooling product due to
foreign matter from the main pipe during the construction, you are advised to
clean the main pipe before water is supplied to the smart cooling product.
Turn off the isolation valves on the water inlet and outlet pipes before the
cleaning and turn them on afterwards.
For details about how to manually adjust the water valve opening, see the
water valve actuator manual or guide.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
52

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-c210h4

Table of Contents