Step 3 Tap Fault Diagnosis_Repair to view the diagnosis report. Rectify the faults
following instructions in the diagnosis report.
Figure 11-4 Diagnosis report
----End
Follow-up Procedure
To query historical alarms, choose Common Function > Query Hist Alarms or
Alarms > Query Hist Alarms on the home screen.

11.1.9 How Do I Clear Runtime?

Context
Performance value clearance can only be performed after component
maintenance. Otherwise, the component may run overtime and weaken the
performance of the unit.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Figure 11-5 Performance Maint screen
Issue 01 (2022-12-30)
NO TE
Historical alarms are displayed by clearance time. The latest cleared alarm is displayed in
the uppermost row.
NO TICE