FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Context
● The external drainpipe must have a downward gradient (> 1:100) along the
drainage direction, and no accumulated water is allowed.
● The entire drainpipe should be closely wrapped with thermal insulation foam.
● Both hoses and rigid pipes can be connected. This section uses rigid pipe
connection as an example.
Drainpipe
Step 1 Apply sealant or wrap sealing tape around the drainpipe port, and install the
water pipe adapter.
Step 2 Wrap the drainpipe with thermal insulation foam and route it through the water
pipe hole at the top of the cabinet.
Step 3 Connect the PPR water pipe using a heat gun and wrap the pipe with thermal
insulation foam.
Figure 4-16 Connecting a drainpipe
Step 4 Connect the drainpipe to the external drainage system.
----End
4.4.2 Connecting Chilled Water Inlet and Outlet Pipes
Context
●
Issue 01 (2022-12-30)
NO TICE
Connect the water inlet and outlet pipes from the inside to the outside and
from the top to the bottom.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
48