Huawei FusionCol8000-C210 User Manual page 83

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Check Item
Electrical
connection
(Optional)
Differential
pressure
sensor
Air damper
(optional)
(Optional)
Water sensor
Issue 01 (2022-12-30)
Expected Result
The water inlet and outlet pipes are
properly installed and secured without
leakage.
The water inlet and outlet pipes are
routed smoothly and are not over-bent.
The drainpipe has a gradient (1:100 is
recommended).
The power supply voltage is the same as
the rated voltage on the equipment
nameplate.
Cables are intact.
No open circuits, short circuits, or
incorrect connections occur in electrical
loops.
The power cables and signal cables are
properly connected.
The ratings of circuit breakers are correct.
Relevant control cables are properly
connected.
All cables, connectors, and screws are
secured.
The cable ties are securely tightened
around the pressure inlet tube.
The pressure inlet tube is not blocked or
bent.
The differential pressure sensor is secured
reliably and steadily.
Cables are connected reliably and steadily.
The air damper and equipment are
secured reliably and steadily by bolts as
required.
Cables to the water sensor are connected
correctly and securely.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
75