CA UTION
– If the main control board is not powered off, after the DP cable is inserted
into the display module, the main control board detects and initializes the
display module. This process takes 10s to 30s. Wait for 5s to 10s. The
indicator on the panel turns on, but the screen does not turn on. Wait for
another 5s to 20s until the screen is restored to the state before the
replacement.
– If the main control board is powered off, power on the main control board
after the DP cable is connected to the display module. After the main
control board is powered on, the startup logo and self-check progress bar
are displayed on the display module. The home screen is displayed. The
whole restoration takes about 60s to 90s.
Power on the unit and tap Start on the home screen. Ensure that the unit is
running normally without any alarms.