Precautions
• If link direct access was performed from the CPU module and Motion module built-in program at the same time, the
processing may not be performed correctly. When performing link direct access with the CPU module and Motion module
built-in program, adjust the access timings to prevent overlap. Or, configure them so that they do not access the same area
(units of 32 points for bit data/units of 2 points for word data).
CPU module
Module built-in program
SET J1\Y101
RY100 := TRUE;
• Even if direct access is made on a link device to which station assignment was not performed in "Network Configuration
Settings" under "Basic Settings", data can be read or written without any error.
• When conducting a link direct access to a motion control station link device, the next operation will occur. The values
written to RX/RWr assigned to the motion control station are not reflected in the output to the motion control. Additionally,
the values written to the motion control station RX/RWr are not stored in the local station link device (RX/RWr). When
reading RX/RWr assigned to the motion control station, the value written last (initial value 0) by link device direct access,
etc. of the link device is read.
Motion module
RY
FALSE
TRUE
RY100
FALSE
RY101
1 FUNCTIONS
37
1.1 Cyclic Transmission