Mitsubishi Electric MELSEC iQ-R Series User Manual page 261

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
SW00F0
CPU operating
to
status of each station
SW00F7
SW0100 to
CPU moderate/major
SW0107
error status of each
station
Description
Stores the CPU operating status of each station.
0: RUN, PAUSE
1: STOP or moderate/major error
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW00F0
16 15 14 13 12 11 10
SW00F1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW00F2
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW00F3
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW00F4
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW00F5
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW00F6
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW00F7
Each No. in the table represents a station No..
 is fixed to 0.
(Conditions)
• Reserved stations and stations that surpass the maximum station No. are ignored.
• Since a local station cannot obtain the station information of the CC-Link IE TSN Class
A remote station when communicating in multicast mode, "0: RUN, PAUSE" is reflected
to the CC-Link IE TSN Class A remote station.
Stores the moderate/major error occurrence status of each station.
0: No moderate/major error
1: Moderate/major error occurring
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0100
16 15 14 13 12 11 10
SW0101
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW0102
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW0103
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW0104
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW0105
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW0106
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW0107
Each No. in the table represents a station No.
 is fixed to 0.
(Condition)
• If an error occurs, the data immediately before the error is held.
• Reserved stations and stations that surpass the maximum station No. are ignored.
• Since a local station cannot obtain the station information of the CC-Link IE TSN Class
A remote station when communicating in multicast mode, "0: No moderate/major error"
is reflected to the CC-Link IE TSN Class A remote station.
• When using PLCopen motion control FB mode, if the communication cycle interval
setting is less than 125 μs, this will be fixed at "OFF: No moderate/major error".
9
8
7
6
5
4
3
2
1
120 119 118 117 116 115 114 113
9
8
7
6
5
4
3
2
1
120 119 118 117 116 115 114 113
Appendix 4 List of Link Special Register (SW)
Availability
PLCopen
Simple
Motion
Motion
control FB
mode
mode
APPX
259
A