Error definition and causes
code
3021H
At startup of data link, an overlapping IP
address among device stations has been
detected.
3040H
Response data of the dedicated
instruction cannot be created.
3060H
The send/receive data size exceeds the
allowable range.
3110H
An instruction was received to enable
network synchronization for a station not
supporting network synchronization.
3111H
An instruction was received to enable
network synchronization for a station not
supporting network synchronization.
3121H
The cyclic transmission setting information
received from the master station exceeds
the setting range.
3130H
Devices with time synchronization priority
of 0 to 15 have been connected.
3135H
Over the number of stations that can be
connected.
3136H
An illegal ring topology was detected.
4 TROUBLESHOOTING
182
4.5 List of Error Codes
Action
Correct the IP addresses of the device stations.
• Increase the request interval.
• Decrease the number of request nodes.
• Wait for a response to the previous request before sending the next
request.
• Correct the timeout value.
• Check and change the send data size of the CC-Link IE TSN-equipped
module or the external device.
• If the same error occurs again even after taking the above, the possible
cause is a hardware failure of the error module or CPU module. Please
consult your local Mitsubishi representative.
Set "Network Synchronous Communication" for the corresponding local
station to "Asynchronous" in "Network Configuration Settings" under "Basic
Settings" of the master station.
• Update the Add-on baseSystem version to "1.16" or later.
• Set "Network Synchronous Communication" for the corresponding local
station to "Asynchronous" in "Network Configuration Settings" under
"Basic Settings" of the master station.
Write the module parameter to the CPU module again. If the same error
occurs again even after taking the above, please consult your local
Mitsubishi representative.
Remove devices with time synchronization priority of 0 to 15, or change the
priority to between 16 and 255.
• Reduce the total number of stations to 31 stations (master station: 1,
device station: 30) or less.
• Reduce the number of stations of CC-Link IE TSN Class B devices to eight
or less for each port of the master station.
Set a line topology or star topology, and turn off and on or reset all stations.
Detailed
information 1
Detailed
information 2
■Operation source
information
• IP address
■IP address
duplication information
• Duplication station 1
MAC address (1st
octet, 2nd octet)
• Duplication station 1
MAC address (3rd
octet, 4th octet)
• Duplication station 1
MAC address (5th
octet, 6th octet)
• Duplication station 2
MAC address (1st
octet, 2nd octet)
• Duplication station 2
MAC address (3rd
octet, 4th octet)
• Duplication station 2
MAC address (5th
octet, 6th octet)
■Grandmaster MAC
address information
• MAC address (1st,
2nd octet)
• MAC address (3rd,
4th octet)
• MAC address (5th,
6th octet)
■