Chapter 1 Functions; Cyclic Transmission - Mitsubishi Electric MELSEC iQ-R Series User Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

1
FUNCTIONS
1.1

Cyclic Transmission

This section describes periodic data communications among stations on the network using link devices.
• The link devices can be assigned in "Network Configuration Settings" under "Basic Settings". (Page 112 "CC-Link IE
TSN Configuration" Window)
• The link refresh is assigned in "Refresh Settings" under "Basic Settings". (Page 100 Refresh Settings)
The cyclic transmission operates as follows with the communication mode set by the module parameter of the master station.
Communication mode
Description
Unicast mode
• Cyclic data is sent to one station.
• When this communication mode is used, the local station cannot receive cyclic data from another station. Use this mode
when there is no local station or when it is not required for the local station to receive cyclic data from another station.
• The cyclic transmission time of this mode is shorter than the cyclic transmission time of multicast mode.
( Page 275 Communication cycle interval)
Multicast mode
• Cyclic data is sent to multiple stations.
• When this mode is used, the local station can receive cyclic data from another station. Use this mode when it is required for
the local station to receive cyclic data from another station.
• The cyclic transmission time of this mode is longer than the cyclic transmission time of unicast mode.
( Page 275 Communication cycle interval)
Assign RX, RY, RWr, and RWw of standard stations to the link device area according to the parameter setting. For the access
to the link device area, refer to the following.
Page 20 Master station and remote stations (standard stations)
For RX, RY, RWr, and RWw of motion control stations, refer to the following.
Page 21 Master station and remote stations (motion control stations)
• When cyclic transmission is performed in multicast mode, the local station cannot receive RX and RWr sent
by the CC-Link IE TSN Class A remote station. (Page 26 Multicast mode)
• To allow the local station to obtain RX and RWr sent by the CC-Link IE TSN Class A remote station, use the
program to send RX and RWr from the master station to the local station.
• In multicast mode, set "Communication Period Setting" for the local station under "Network Configuration
Settings" to "Basic Period".
• If a data link error occurs in multicast mode, ERR LED at the local station flashes. However, even if a data
link error occurs at the CC-Link IE TSN Class A remote station during data link, ERR LED at the local station
does not flash. (The LED remains off.)
• In multicast mode, 'Data link error status of each station' (SB00B0) and 'Total number of device stations
present value' (SW0059) at the local station can be checked by SB and SW. However, the information on
the CC-Link IE TSN Class A remote station may not be checked by some SB and SW.
Precautions
The Motion module provides the following CPU operating status notifications for Motion control stations.
PLC ready status
Motion module stop (moderate/
major) error detection status
ON
OFF
Error not detected
Error detected
CPU operating status notification for Motion control stations
For Add-on baseSystem
version "1.22" or earlier
CPU RUN
CPU error stop
(CPU RUN when not set to an axis)
For Add-on baseSystem
version "1.24" or later
CPU RUN
CPU STOP
CPU error stop
1 FUNCTIONS
1.1 Cyclic Transmission
1
19

Advertisement