Required Settings; Station Type; Network No - Mitsubishi Electric MELSEC iQ-R Series User Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

2.2

Required Settings

Set the station type or IP address of the Motion module.
Item

Station Type

Network No.

Station No./IP Address Settings
Station Type
Set the station type of the Motion module.
Item
Station Type
Network No.
Set the network No. of the own station of the Motion module.
Item
Network No.
Precautions
Set a network No. that does not overlap any other network Nos.
In particular, when an Ethernet-equipped module (CPU module) is used at default, the IP address is 192.168.3.39 and the
network No. is the third octet of the IP address, thus 3. Because setting the network No. of the Motion module to 3 causes an
overlap, set another network No.
Description
Set the station type of the Motion module.
Set the network No. of the Motion module.
Set the IP address of the Motion module.
Description
The Motion module is used as the master station.
Only one master station can be set in a network.
Description
Set the network No. of the Motion module.
Reference
Page 97 Station Type
Page 97 Network No.
Page 98 Station No./IP Address Settings
Setting range
Setting range
1 to 239
(Default: 1)
2 PARAMETER SETTINGS
2.2 Required Settings
2
97