Mitsubishi Electric MELSEC iQ-R Series User Manual page 116

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Simple
Detailed
display
display
RWr Setting
RWw Setting
*7
LB Setting
LW
*7
Setting
Parameter Automatic
Setting
PDO Mapping Setting
IP Address
Subnet Mask
Default Gateway
Reserved/Error Invalid
Station
Network Synchronous
*10
Communication
Communication Period
*11*12
Setting
Station Information
2 PARAMETER SETTINGS
114
2.5 "CC-Link IE TSN Configuration" Window
Description
Assign RWr/RWw points in increments of 4. ( Page 20 Communications
using RX, RY, RWr, and RWw)
Modules with settings provided by the device profile are automatically set from
selected models. (Excluding modules with a number of points that is not fixed)
■When the GX Works3 version is earlier than "1.085P".
<When using PLCopen Motion control FB mode>
• For the motion control station, only the number of points is set.
<When using Simple Motion mode>
• For the motion control station, settings cannot be made.
Assign LB points in increments of 16 and LW points in increments of 1. (Page
27 Communications using LB and LW)
Modules with settings provided by the device profile are automatically set from
selected models. (Excluding modules with a number of points that is not fixed)
Set whether to set the parameters of each device station automatically.
This cannot be set for extension modules. However, the parameter automatic
setting of extension modules is interlocked with the settings of the connected
main module.
Set the PDO mapping to the station that supports CANopen communications.
(Page 125 PDO mapping setting)
• When using Simple Motion mode, settings cannot be made for the motion
control station.
Set the IP address of a station that performs cyclic transmission.
Set a subnet mask to identify a network address.
Set the same value for the master station and device station. Even if a device
station has a different subnet mask from the master station, it does not result in
an input error.
If 255.255.255.255 is set, leave it empty.
Set the default gateway address to connect to the external network.
If 223.255.255.255 is set, leave it empty.
Set the device station as a reserved station or error invalid station.
• No Setting: The device station is connected to the network.
• Reserved Station: The device station is reserved in the parameters for future
expansion. By using a reserved station, link device assignment will not change
even if the device station is added (reservation is canceled). Therefore,
modification of the program is not required. Physical connection of the device
station on the network is not required.
• Error Invalid Station: Even if a device station is disconnected during data link,
the master station will not detect the device station as a faulty station.
Set whether to synchronize each device station with network synchronous
communication.
When multiple communication cycles are set, set the cycle of each device station.
(Page 45 Communication cycles coexistence)
■Alias
Enter the name of a device if required.
The entered device name is displayed in "Network Status" in the "CC-Link IE
TSN/CC-Link IE Field Diagnostics" window.
For the extension module of the remote station, the name is not displayed in the
"CC-Link IE TSN/CC-Link IE Field Diagnostics" window, even if entered.
■Comment
Information entered in "Comment1" on the "Properties" window displayed by
right-clicking the module in the list of stations or the network map is displayed.
■Station-specific mode setting
Set the station-specific mode of the device station. (Only when the device station
supports the station-specific mode)
Setting range
• Number of points: No point,4 to 8192
• Start: 0000H to 1FFCH
• End: 0003H to 1FFFH
(Default: Varies depending on the set module)
• Number of points: No point, 16 to 32768
• Start: 0000H to 7FF0H
• End: 000FH to 7FFFH
(Default: Varies depending on the set module)
• Number of points: No point, 1 to 16384
• Start: 0000H to 3FFFH
• End: 0000H to 3FFFH
(Default: Varies depending on the set module)
• Checked: Distribute parameters
• Not checked: Do not distribute parameters
(Default: Not checked)
0.0.0.1 to 223.255.255.254
(Default: The first to third octets have the
same values as the master station, the fourth
octet has a serial No. from 1 to 254)
0.0.0.1 to 255.255.255.255
(Default: The same value as the master
station, or 255.255.255.0 if there is no master
station)
• 0.0.0.1 to 223.255.255.254 (When the
address is inputted by decimal values)
• Empty (0.0.0.0)
• No Setting
*8
• Reserved Station
*9
• Error Invalid Station
(Default: No setting, master station is fixed as
empty)
• Synchronous
• Asynchronous
(Default: Asynchronous)
• Basic Period
• Normal-Speed
• Low-Speed
(Default: Basic Period)
Up to 32 one-byte characters (one-byte or
two-byte)
(Default: empty)
Up to 32 one-byte characters (one-byte or
two-byte)
(Default: empty)
The setting varies depending on the set
device station.