No.
Name
SW0060
Communication
cycle intervals
SW0061
System reserved
time
SW0062
Cyclic transmission
time
SW0063
Transient
transmission time
SW0064
Multiple cycle setting
(medium speed)
SW0065
Multiple cycle setting
(low speed)
SW0066
Connection status of
own station
SW0072
Communication
cycle intervals
(Calculation value)
SW0073
Cyclic transmission
time (Calculation
value)
SW0074
PORT1 cable
disconnection
detection count
SW0075
PORT1 receive error
detection count
SW0076
PORT1 total number
of received data
(lower 1 word)
SW0077
PORT1 total number
of received data
(upper 1 word)
SW0078
Transient
transmission time
(Calculation value)
SW0079
Watch dog counter
processing time
(calculation value)
SW007A
Transient
transmission addition
time (calculation
value)
SW007C
PORT2 cable
disconnection
detection count
APPX
256
Appendix 4 List of Link Special Register (SW)
Description
Stores the setting value of the communication cycle intervals set with the module
parameter of the master station. (Unit: s)
Stores the setting value of the system reserved time set with the module parameter of the
master station. (Unit: s)
Stores the setting value of the cyclic transmission time set with the module parameter of
the master station. (Unit: s)
Stores the setting value of the transient transmission time set with the module parameter
of the master station. (Unit: s)
Stores the setting value of the multiple cycle setting (medium speed) set with the module
parameter of the master station.
Stores the setting value of the multiple cycle setting (low speed) set with the module
parameter of the master station.
Stores the connection status of the own station.
00H: Normal (communication in progress on P1 and P2)
01H: Normal (communication in progress on P1, cable disconnected on P2)
10H: Normal (cable disconnected on P1, communication in progress on P2)
11H: Disconnected (cable disconnected on P1 and P2)
12H: Disconnected (cable disconnected on P1, establishing line on P2)
21H: Disconnected (establishing line on P1, cable disconnected on P2)
22H: Disconnected (establishing line on P1 and P2)
Stores the communication cycle intervals that were calculated by the number of device
stations and the points set in "Network Configuration Settings" of "Basic Settings". (Unit:
s)
Stores the cyclic transmission time that was calculated by the number of device stations
and the points set in "Network Configuration Settings" of "Basic Settings". (Unit: s)
Stores the cumulative count of cable disconnections detected at the PORT1 side.
When 'Clear communication error count' (SB0006) is turned on, the stored count is
cleared.
When FFFFH (maximum value 65535) is counted, the value returns to 0 and the module
continues to count.
Stores the cumulative count of error data receptions at the PORT1 side.
The count stores only error data that is not transmitted to all stations.
When 'Clear communication error count' (SB0006) is turned on, the stored count is
cleared.
When FFFFH (maximum value 65535) is counted, counting stops.
Stores the cumulative count of data receptions at the PORT1 side.
When 'Clear communication error count' (SB0006) is turned on, the stored count is
cleared.
When FFFFFFFFH (maximum value 4294967295) is counted, counting stops.
Stores the transient transmission time that are calculated by the number of device
stations and the number of link device points set in "Network Configuration Settings" of
"Basic Settings". (Unit: s)
Stores the processing time for checking the watch dog counter calculated from the device
stations which are actually connected. (Unit: s)
Stores the time which needs to be added to "Communication Period Interval Setting" and
"Transient Transmission Time" set in "Communication Period Setting" under "Basic
Settings". (Unit: s)
Stores the cumulative count of cable disconnections detected at the PORT2 side.
When 'Clear communication error count' (SB0006) is turned on, the stored count is
cleared.
When FFFFH (maximum value 65535) is counted, the value returns to 0 and the module
continues to count.
Availability
PLCopen
Simple
Motion
Motion
control FB
mode
mode

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd78g4Rd78g8Rd78g16Rd78g32Rd78g64Rd78ghv ... Show all

Table of Contents