Mitsubishi Electric MELSEC iQ-R Series User Manual page 168

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Check item
When the communication speed setting of the master station is set to 1 Gbps,
is the total cyclic data size of all device stations on the 100 Mbps device side
at the boundary between CC-Link IE TSN Class B 1 Gbps devices other than
the master station and CC-Link IE TSN Class B 100 Mbps devices exceeding
2K bytes?
Is the total cyclic data size of all device stations on the CC-Link IE TSN Class
A device side at the boundary between CC-Link IE TSN Class B devices other
than the master station and CC-Link IE TSN Class A devices exceeding 2K
bytes?
In multicast mode, is the CC-Link IE TSN Class A remote station connected to
a local station or remote station that does not support the multicast filter?
■When the version of Add-on baseSystem is "1.20 to 1.22"
Is a CC-Link IE TSN Class A device that supports the CANopen profile with
the protocol version 2.0 connected?
■ When the Motion module with the baseSystem version of "1.15" or earlier is used
When the Motion module with the baseSystem version of "1.15" or earlier is used, check the following.
Check item
When "Communication Speed" of the master station is set to "1 Gbps" and a
CC-Link IE TSN Class B/A device with a communication speed of 100 Mbps
is used, does the station repeat disconnection and return even if
"Communication Period Setting" is set to "Low-Speed"?
Communications are unstable
When cyclic data transfer processing time or transmission delay time is long or when a transient transmission timeout
occurred, check the following items.
Check item
Is the L ER LED of the Motion module turned on?
Is the ambient temperature for the module outside the specified range?
Is any error shown in "Selected Station Communications Status Monitor" of
CC-Link IE TSN/CC-Link IE Field diagnostics?
Is there any noise affecting the system?
4 TROUBLESHOOTING
166
4.4 Troubleshooting by Symptom
Action
• Restrict the number of stations to be connected so that the total cyclic data
size of 100 Mbps devices does not exceed 2K bytes.
• Connect 100 Mbps devices to the master station.
• Restrict the number of stations to be connected so that the total cyclic data
size of CC-Link IE TSN Class A devices does not exceed 2K bytes.
• Connect CC-Link IE TSN Class A devices to the master station.
• Connect the local station or remote station supporting the multicast filter to
the CC-Link IE TSN Class A remote station.
• Set unicast mode.
Update the master station firmware to Add-on baseSystem version "1.24" or
later.
Action
Use the following wiring and setting.
• Use only either P1 or P2 of the master station.
Action
If turned on, perform troubleshooting for a case when the L ER LED is turned
on. ( Page 142 When the L ER LED turns on)
Keep the ambient temperature within the specified range by taking action
such as removing heat source.
If an error is identified at P1 or P2, perform a cable test.
Change the placement and/or wiring of the modules so that the system is not
affected by noise.