Mitsubishi Electric MELSEC iQ-R Series User Manual page 34

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting method
The link refresh is assigned in "Refresh Settings" under "Basic Settings". (Page 100 Refresh Settings)
Precautions
■ Latched devices of the CPU module
If data in latched devices of the CPU module are cleared to 0 on a program when the CPU module is powered off and on or
reset, the data may be output without being cleared to 0, depending on the timing of the cyclic data transfer processing and
link refresh.
CPU module device
Latch relay (L), file register (R, ZR)
CPU module device within the latch range
*1 For the initial device value setting of the CPU module, refer to the following.
GX Works3 Operating Manual
■ For link refresh to RX, RWw, RWr assigned to the Motion control station
• The refreshed value for RY/RWw assigned to the motion control station is not reflected in the output to the motion control
station. Additonally, when operating in multicast mode, the value refreshed to RY/RWw assigned to the motion control
station is not stored in the local station link device (RX/RWr).
• When refreshing RX and RWr, the value (initial value 0) written last by direct access, etc. of the link device is stored in the
CPU side device for RX/RWr assigned to the motion control station.
1 FUNCTIONS
32
1.1 Cyclic Transmission
How to disable the device data
The device value is cleared to 0 by using the initial device value of the CPU module.
Delete all the latch range settings specified in "Latch Interval Operation Setting" under "Device Latch Interval
Setting" in "Memory/Device Setting" of "CPU Parameter".
*1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd78g4Rd78g8Rd78g16Rd78g32Rd78g64Rd78ghv ... Show all

Table of Contents