Figure 4-26 Teamwork communications cable and FE monitoring communications
cable
(1) Orange-white
(5) Blue-white
Figure 4-27 RS485 monitoring communications cable
(4) Blue
----End

4.6.2 FE Teamwork + FE Monitoring

Step 1 Connect teamwork and monitoring communications cables.
Networking
Protocol
Description
Issue 05 (2022-12-15)
(2) Orange
(6) Green
FE Teamwork
MAC_CAN
A teamwork network supports
a maximum of 16 units.
NO TE
● If the Modbus-TCP/SNMP protocol is used, customers can purchase the NetEco (a LAN
switch is required) or a third-party NMS as the monitoring system.
● If the number of units in a group is greater than 16, FE teamwork needs to be
implemented by group. For example, if the number of units under teamwork is 18, they
can be divided into two groups, for example, 9+9, 16+2, or 10+8.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
(3) Green-white
(4) Blue
(7) Brown-white
(8) Brown
(5) Blue-white
FE Monitoring
Modbus-TCP/SNMP
-
61