Installation Requirements
Table 3-3 Installation requirements
Item
Room door
Elevator
Pipe routing mode
Maintenance space
Power distribution
a: Applicable to the pallet truck located on the side. If the pallet truck is located
on the display module or fan side, the door width must be greater than or equal
to 2.5 m.
Issue 05 (2022-12-15)
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Product Specifications
Specifications
a
Width ≥ 1.3 m
; height ≥ 2.5 m
Elevator door height ≥ 2.5 m, door
width ≥ 1.3 m, and car depth ≥ 2.5 m
Top pipe routing
For details, see the equipment room
layout requirements.
Leakage circuit breakers are not
recommended for the main power
route. If leakage circuit breakers are
required by the customer or by local
regulations, use the residual current
circuit breaker (RCCB) that is not
sensitive to the single-phase DC pulses
and transient current pulses.