Step 2 Tap Clear of a specific performance parameter to clear its runtime.
----End

11.1.10 How Do I Calibrate a Sensor?

Context
Calibrate a sensor if the displayed temperature or humidity values on the sensor
deviate from the actual values. For example, if the return air temperature
measured by other precise temperature measurement units at the return air
monitoring point is 20°C but the return air temperature detected by the unit is
22°C, the sensor has an error of 2°C. In this case, you can set the return air
temperature calibration value to –2°C.
Procedure
Step 1 Choose Maint > Sensor Calibration on the home screen.
Step 2 Fill the calibration value based on the measured error.
----End

11.1.11 How Do I Change the Password?

Prerequisites
Procedure
Step 1 On the home screen, choose Settings > User Settings. The User Settings screen is
displayed.
Figure 11-6 User Settings
Issue 05 (2022-12-15)
To modify a password, log in as the admin user or operator user.
You can only modify the password of the current user.
NO TE
You can set LCD password complexity check to Enable or Disable and set the complexity
of the password.
If a password with low complexity is set, the system will display a message indicating that
the password complexity is low and asking you to set a new one. Examples of low
complexity passwords: H#uawei123, Password and openasadminAdmin23@#.