Connecting The Chilled Water Inlet And Outlet Pipe - Huawei FusionCol8000-C210 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Context
Procedure
Step 1 Pull the hose to the top of the cabinet and route the hose through the humidifier
water inlet pipe hole.
Figure 4-17 Connecting the humidifier water inlet pipe
Step 2 Connect the water inlet pipe of the smart cooling product to the engineering pipe.
----End

4.4.3 Connecting the Chilled Water Inlet and Outlet Pipe

Context
Issue 05 (2022-12-15)
NO TE
A humidifier water inlet hose is delivered with the unit. Route the hose along the reserved
pipe clamp on the cabinet side to the top of the cabinet.
NO TE
Before connecting the water inlet pipe of the smart cooling product to the engineering pipe,
clean the engineering pipe to prevent foreign matter from entering the humidifier.
Connect the water inlet and outlet pipes from the inside to the outside and
from the top to the bottom.
Water inlet and outlet pipes are connected using thread connectors.
Tools: 70# open-end wrench, 36# open-end wrench, 18# pipe wrench, sealant
(used for pasting thermal insulation foam), thread sealant
Copyright © Huawei Digital Power Technologies Co., Ltd.