FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Figure 4-5 Humidifier water inlet pipe
(1) Internal thread connector: G 1/2 in.
(reserved port on the unit)
(3) Rigid pipe: made of PP-R or other materials
4.2.2.3 Chilled Water Inlet and Outlet Pipes
Figure 4-6 Connecting the water inlet or outlet pipe
(1) Internal thread connector: G 2 in. (reserved
port on the unit)
4.2.2.4 Pipe Support
Determine the support appearance based on the site requirements.
Issue 05 (2022-12-15)
NO TE
The pressure bearing capacity of the humidifier pipe is 0.1–0.7 MPa.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
(2) Adapter: G 1/2 inch, connected to a rigid
pipe with external threads
(2) Seamless steel pipe with external threads:
DN50 seamless steel pipe connector with
external threads