Replacing A Water Valve Actuator - Huawei FusionCol8000-C210 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Step 3 (Optional) Remove the air damper.
Step 4 Remove the fan guard.
Step 5 After the electric heater cools down to the normal temperature, cut off the cable
tie on the electric heater cable and remove the cable interconnection terminal.
Step 6 Remove the four bolts from both ends of the electric heater and take out the
electric heater.
Figure 10-5 Removing an electric heater
Step 7 Install and secure the new electric heater.
Step 8 Reinstall the fan guard.
Step 9 (Optional) Reinstall the air damper.
Step 10 Power on the unit, tap Start on the home screen, choose Maintenance > Startup
Wizard, and commission the electric heater to check that it works properly before
you exit.
Step 11 On the home screen, choose Maintenance > Performance Maintenance to enter
the Performance Maintenance screen and clear the runtime of the electric
heater.
----End

10.6 Replacing a Water Valve Actuator

Context
Issue 05 (2022-12-15)
A water valve actuator needs to be replaced.
A spare water valve actuator of the same model is available and functional.
Tools: diagonal pliers and cable ties