Huawei FusionCol8000-C210 User Manual page 145

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
3.
4.
5.
6.
----End
Issue 05 (2022-12-15)
Use a Phillips screwdriver to remove the four screws and gaskets that secure
the display module, and pull out the display module.
NO TICE
– When pushing the display module leftwards or rightwards, pay attention to
the buckles on the panel to prevent damage to the display module.
– The gasket is used to adjust the distance between the display module and
the door panel.
– The gasket dimensions are 25 mm (L) x 12 mm (W) x 2 mm (H) and the
center aperture is 6 mm.
Install the new display module in the original position by performing the
preceding steps in reverse order.
Connect the control signal cable to the display module
CA UTION
– If the main control board is not powered off, after the DP cable is inserted
into the display module, the main control board detects and initializes the
display module. This process takes 10s to 30s. Wait for 5s to 10s. The
indicator on the panel turns on, but the screen does not turn on. Wait for
another 5s to 20s until the screen is restored to the state before the
replacement.
– If the main control board is powered off, power on the main control board
after the DP cable is connected to the display module. After the main
control board is powered on, the startup logo and self-check progress bar
are displayed on the display module. The home screen is displayed. The
whole restoration takes about 60s to 90s.
Power on the unit and tap Start on the home screen. Ensure that the unit is
running normally without any alarms.
Copyright © Huawei Digital Power Technologies Co., Ltd.