After replacing the wet film humidifier, properly install and secure the humidifier
water inlet pipe. Otherwise, the pipe may leak.
Step 7 Install the middle air filter and switch on the active and standby input circuit
breakers of the smart cooling product.
Step 8 Power on the unit, tap Start on the home screen, choose Maintenance > Wizard
Startup, and commission the wet film humidifier to check that it works properly
before you exit.
Step 9 On the home screen, choose Maintenance > Performance Maintenance to enter
the Performance Maint screen, and clear the runtime of the wet film humidifier.
----End

10.3 Replacing a Differential Pressure Switch

Context
Tool: Phillips screwdriver
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Exercise caution because the unit is still energized after it is shut down on the
screen of the display module.
Step 2 Open the electric control box, turn off the active power switch QF1 and standby
power switch QF2, and remove the air filter in the middle.
Step 3 Remove the pressure tube.
Step 4 Unscrew the differential pressure switch using a Phillips screwdriver and take out
the switch.
Issue 05 (2022-12-15)