FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Context
The parameters in this section are for reference only. Set actually parameter values
as required.
Procedure
Step 1 On the home screen, tap
Settings screen, as shown in
Figure 5-6 Teamwork Settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Air conditioner address, Enable teamwork CAN
resistor, Teamwork function and Networking mode can be set on slave smart
cooling products. Other parameters of the slave units will be modified by the
master unit synchronously.
Table 5-5 Teamwork settings
Parameter
Teamwork group num
System address
Issue 05 (2022-12-15)
System address: The address (configurable range: 1–32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
delivers group data. The recommended value range is 1 to the number of
units in the group.
Copyright © Huawei Digital Power Technologies Co., Ltd.
> Teamwork Settings, to enter the Teamwork
Figure
5-6.
Table 5-5
describes how to set the parameters.
Description
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the planned unit address. The addresses of
units in the same teamwork group must be unique.
5 Power-On Commissioning
85