FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Tab
T/H Sensor
Issue 05 (2022-12-15)
Parameter
Heating function
Heating mode
Humidifying
function
Dehumidifying
function
Floor water
overflow alarm
action
In-cabinet water
overflow alarm
action
Temperature and
humidity control
type
Temperature
setpoint
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Power-On Commissioning
Description
If Enable is selected, the electric heater can
be started when the ambient temperature is
lower than the temperature setpoint by a
certain range. If Disable is selected, the
heating function is disabled. If Enabled
when active power is selected, the electric
heater can be started only when the active
power supply is used and the ambient
temperature is lower than the temperature
setpoint by a certain range.
If Dehumidifying heating is selected, the
electric heater determines whether to start
based on the current temperature only
when the dehumidification function is
enabled. If Low-temperature heating is
selected, the electric heater is started only
based on temperature requirements,
regardless of whether the dehumidification
function is enabled. If Dehumid & low-
temp heat is selected, the electric heater
determines whether to start based on the
temperature requirements when the
dehumidification and heating conditions are
met.
The humidifying function can be set to
Enable, Disable, or Enabled when active
power.
The dehumidifying function can be set to
Enable, Disable, or Enabled when active
power.
Set this parameter to Shutdown, Inactivity,
Only indoor fan running, or Humidifier
stopped based on site requirements.
Set this parameter to Shutdown, Inactivity,
Only indoor fan running, or Humidifier
stopped based on site requirements.
Cold aisle, Hot aisle, Return air, or Supply
air can be set as required. The temperature
and humidity setpoints corresponding to the
selected control type are enabled.
After the temperature and humidity control
type and the temperature value under this
type are set, the unit performs cooling
based on the settings.