Figure 4-30 Removing the transport fasteners from the compressor
Step 2 Remove the transport fasteners.
Step 3 Tighten the bolts on the compressor again to a torque of 12 N·m.
----End

4.4.4 Securing the Cabinet

Procedure
Step 1 Determine the position for installing the cabinet.
Step 2 Drill a hole in each mounting hole position using a hammer drill.
Step 3 Move the cabinet over its castors to the installation position.
Step 4 Level the cabinet using an adjustable wrench, as shown in
Before leveling the cabinet, use a measuring tape to check that the vertical
distance between the top of the cabinet and the floor is 2000 mm (+3 mm) for a
2000 mm high cabinet or 2200 mm (+3 mm) for a 2200 mm high cabinet. Ensure
that the cabinet is level using a level.