Figure 11-35 Installing a liquid level detector
Step 7 Install the water pan cover, and close the front door.
Step 8 Power on the device and tap Startup on the home screen. Ensure that the smart
cooling product is running normally without any alarms.
----End

11.11 Replacing a Condensate Pump

Prerequisites
Before removing the condensate pump, drain water from the water pan
completely.
Context
The condensate pump can be maintained only from the front door.
Procedure
Step 1 Tap Shutdown on the home screen of the controller, and turn off the active power
switch QF1 and standby power switch QF2. (For the model with a single power
supply, you do not need to turn off QF2.)
Issue 08 (2021-09-17)
A condensate pump needs to be replaced.
A spare condensate pump of the same model is available and functional.
Tools: Phillips screwdriver, flat-head screwdriver, socket wrench