Huawei NetCol5000-A050 User Manual page 140

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Menu
Settings >
Quick Settings
> Teamwork
Settings
Settings >
Quick Settings
> System
Optional Parts
Issue 08 (2021-09-17)
Parameter
Teamwork
group No.
System
address
Teamwork
function
Networking
mode
Cold aisle
sensor 1–5
Hot aisle
sensor 1–5
Low
temperature
component
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Description
Specifies the teamwork
group number. The
teamwork group
numbers in the same
group must be the
same. A maximum of
four groups (1–4) can
be set.
The addresses of units
in the same teamwork
group cannot be the
same.
Specifies whether to
enable the teamwork
function. If no, the unit
operates
independently. If yes,
the unit operates in a
team with other units.
Specifies the
networking mode for
teamwork control. The
networking mode
selected on the screen
must match the actual
networking mode.
Otherwise, the
teamwork function is
unavailable. CAN
network indicates
teamwork control over
a CAN bus. MAC_CAN
network indicates
teamwork control over
an FE port.
If a temperature and
humidity sensor
outside the cabinet is
installed, set the
temperature and
humidity sensor in the
corresponding position
to Enable.
Specifies whether a
low temperature
component is used.
Setting Guide
Smart cooling
products in the
same aisle (or in
the same area) can
be grouped and use
the same group
number.
Set the planned
unit address.
Set this parameter
based on the onsite
device heat
distribution.
CAN network
Disable
Disable
-
130