Huawei NetCol5000-A050 User Manual page 158

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
If the teamwork control succeeds, the teamwork topology of the smart cooling
product in the group is displayed, as shown in
the note for the screen.
Figure 6-12 Teamwork topology
Table 6-8 Notes for the screen
No.
1
2
3
4
5
Issue 08 (2021-09-17)
Item
Note
On/Off
On indicates that the smart cooling product is started and
Off indicates that the smart cooling product is shut down.
01, 02, 03
Indicates the device address. The minimum address is the
master one and the rest are all slave ones.
NOTE
If the master one is offline, the online device with the smallest
address is selected to be the new master.
Active/
Active: properly responds to the requirement control.
Standby
Standby: responds to the requirement control when active
one is faulty (critical alarms, shutdown, and offline) or
cannot meet cooling requirements.
M/S
M indicates the master unit, and S indicates a slave unit.
Blue indicates that the device is operating, and gray
indicates that the device is idle.
Frame:
A device with green frame indicates the device itself,
green/non-
green
as shown in
A non-green frame indicates the other device in the group,
as shown in