Step 6 Power on the device, choose Maint > Performance Maint on the home screen to
access the performance maintenance screen, and clear the total runtime of the
condensate pump.
Step 7 Tap Startup on the home screen. Ensure that the smart cooling product is running
normally without any alarms.
----End

11.12 Replacing a Wet Film Humidifier

Prerequisites
Context
The wet film humidifier can be maintained only from the rear door.
Procedure
Step 1 Tap Shutdown on the controller home screen.
Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Open the rear door and remove the air filter.
Step 3 Turn off the active power switch QF1, standby power switch QF2 (you do not need
to turn off QF2 for the model with a single power supply), and drive switch QF3.
Step 4 Remove the wet film humidifier.
Figure 11-40 Removing a wet film humidifier
Issue 08 (2021-09-17)
A wet film humidifier needs to be replaced.
A spare wet film humidifier of the same model is available and functional.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
11 Parts Replacement
282