Follow-up Procedure
After powering on, the compressor starts preheating, and the system generates an
alarm indicating that the compressor is preheating (for 12 hours). Do not start the
Issue 08 (2021-09-17)
Parameter
Temperature
setpoint
Humidity
setpoint
Modbus
Comm
address
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Description
After the temperature
and humidity control
type and the
temperature value
under this type are set,
the device performs
cooling or heating
based on the settings.
After the temperature
and humidity control
type and the humidity
value under this type
are set, the device
performs humidifying
or dehumidifying
based on the settings.
Enter the
communications
address of the smart
cooling product as
planned. The NMS
communicates with the
smart cooling product
using this address, and
the communications
addresses of two smart
cooling products
connected to the same
NMS must be different.
Setting Guide
Set this parameter
as required.
● Return air
temperature: 26–
35°C
recommended
● Supply air
temperature: 18–
24°C
recommended
● Cold aisle
temperature: 18–
24°C
recommended
● Hot aisle
temperature: 26–
35°C
recommended
Set this parameter
as required.40%–
60% RH
recommended
Set this parameter
based on NMS
planning.