Huawei NetCol5000-A050 User Manual page 233

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Alarm
ID
A281-4
0
A281-8
0
A281-0
4
A281-0
8
Issue 08 (2021-09-17)
Alarm Name
Alar
m
Seve
rity
Power voltage
MAJ
abnormal
OR
Power voltage
MAJ
abnormal
OR
Power voltage
MAJ
abnormal
OR
Power voltage
MAJ
abnormal
OR
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
1. The power
supply voltage
exceeds the upper
threshold.
2. The SPD and
voltage detection
board is faulty.
1. The power
supply voltage
exceeds the upper
threshold.
2. The SPD and
voltage detection
board is faulty.
1. The power
supply voltage is
below the lower
threshold.
2. The cables to
the SPD and
voltage detection
board are loose or
damaged.
3. The SPD and
voltage detection
board is faulty.
1. The power
supply voltage is
below the lower
threshold.
2. The cables to
the SPD and
voltage detection
board are loose or
damaged.
3. The SPD and
voltage detection
board is faulty.
9 Alarm Reference
Solution
1. Check that the power
supply voltage is within
the operating range.
2. Replace the SPD and
voltage detection
board.
1. Check that the power
supply voltage is within
the operating range.
2. Replace the SPD and
voltage detection
board.
1. Check that the power
supply voltage is within
the operating range.
2. Check the cable
connection to the SPD
and voltage detection
board.
3. Replace the SPD and
voltage detection
board.
1. Check that the power
supply voltage is within
the operating range.
2. Check the cable
connection to the SPD
and voltage detection
board.
3. Replace the SPD and
voltage detection
board.
223

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents