2.
Step 4 Remove the hose clamps on the condensate pump pipes and the condensate
pump using a flat-head screwdriver, pull out the hose, and take out the
condensate pump, as shown in
Figure 11-38 Removing a condensate pump
Step 5 Install the new condensate pump and reinstall the condensate pump assembly in
the cabinet. Connect the water pipe and secure it using hose clamps. Connect the
condensate pump power cable.
Figure 11-39 Installing a condensate pump
Issue 08 (2021-09-17)
Remove the three screws that secure the condensate pump assembly using a
socket wrench, and pull out the condensate pump assembly.