NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Alarm
ID
A048-0
1
Issue 08 (2021-09-17)
Alarm Name
Alar
m
Seve
rity
Supply air
CRITI
high
CAL
temperature
alarm
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
1. The
temperature
sensors or
temperature and
humidity sensors
are located in
inappropriate
positions.
2. The thermal
load power is high
or the cooling
capacity is
insufficient.
3. The ambient
temperature
exceeds the upper
threshold.
4. The high
temperature alarm
threshold is
inappropriate.
5. The value
detected by the
temperature
sensor or
temperature and
humidity sensor is
different from the
actual value.
9 Alarm Reference
Solution
1. Adjust the positions
of the temperature
sensors or temperature
and humidity sensors.
2. Add air conditioners
or contact Huawei
technical support.
3. Measure the ambient
temperature. Check
whether other causes
exist if the alarm
persists in a long time
after startup.
4. Adjust the high
temperature alarm
threshold.
5. Calibrate or replace
the temperature sensor
or temperature and
humidity sensor.
194