Huawei NetCol5000-A050 User Manual page 162

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Step 2 On the home screen, choose Settings > Comm Settings > Modbus Settings and
set Link mode to Server and client or Client. Set Client encryption to Enable.
Figure 6-17 Modbus Settings 1
Figure 6-18 Modbus Settings 2
Step 3 Enter the actual IP address of the NMS.
Step 4 When Client encryption is set to Enable, set NMS port number to 32907. When
Client encryption is set to Disable, set NMS port number to 32906.
Issue 08 (2021-09-17)
NO TE
If the DHCP server is configured on the NMS, select Auto (DHCP). If no, set this parameter
to Manual.
NO TE
The encryption mode must be the same as it on the NMS.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
152