NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Alarm
ID
A28B-0
2
Issue 08 (2021-09-17)
Alarm Name
Alar
m
Seve
rity
Compressor
CRITI
high discharge
CAL
temperature
alarm
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
1. The refrigerant
leaks.
2. The condenser
fins are dirty or
blocked.
3. The ambient
temperature
exceeds the upper
threshold.
4. The
temperature
displayed by the
exhaust air
temperature
sensor is different
from the actual
temperature.
5. The input power
of the outdoor
unit has an open
phase, incorrect
phase sequence,
or is unavailable.
6. Cables to the
indoor and
outdoor units are
not properly
connected.
7. The outdoor fan
or its drive is
faulty.
8. The exhaust fan
is faulty.
9 Alarm Reference
Solution
1. Identify and repair
the leaking point, and
refill refrigerant after
maintenance.
2. Clean the condenser
fins.
3. Measure the ambient
temperature.
4. Calibrate or replace
the temperature sensor.
5. Check the input
power of the outdoor
unit.
6. Check the cables to
the indoor and outdoor
fans.
7. Maintain or replace
the outdoor fan or its
drive.
8. Maintain or replace
the exhaust fan.
228