NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Paramete
r
Cold aisle
temperatu
re and
humidity
sharing
Hot aisle
temperatu
re and
humidity
sharing
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step 1
Issue 08 (2021-09-17)
Description
This function can be
enabled only when at least
one smart cooling product
in the group is equipped
with cold aisle T/H sensors.
If this function is enabled,
the master unit in the
teamwork group collects
the cold aisle temperature
and humidity values from
all units equipped with cold
aisle sensors, and
synchronizes the
temperature and humidity
values after logical
calculation to all units.
NOTE
After this function is enabled,
the master unit synchronizes
the temperature and humidity
control type and setpoints to
all slave units.
This function can be
enabled only when at least
one smart cooling product
in the group is equipped
with hot aisle T/H sensors.
If this function is enabled,
the master unit in the
teamwork group collects
the hot aisle temperature
and humidity values from
all units equipped with hot
aisle sensors, and
synchronizes the
temperature and humidity
values after logical
calculation to all units.
NOTE
After this function is enabled,
the master unit synchronizes
the temperature and humidity
control type and setpoints to
all slave units.
and
Step
2.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Setting Rule
This parameter can be
enabled when there
are at least one smart
cooling products in
the group are
configured with cold
aisle T/H sensors.
This parameter can be
enabled when there
are at least one smart
cooling products in
the group are
configured with hot
aisle T/H sensors.
Default
Value
Disable
Disable
147